Xi'an Hongxin Arc Furnace Company Limited
Online Service

Online Service

SAF And EAF Parameter Electrical Measurement Instruments 0~999MW Power

SAF And EAF Parameter Electrical Measurement Instruments 0~999MW Power

Basic Properties

country of origin
China
brand name
Hongxin

Trading Properties

unit price
Negotiable
payment method
T/T,Western Union,D/P,D/A,L/C

Product Summary

Electrical Parameter Measurement Instruments SAF and EAF are high-current, low-voltage equipment requiring precise measurement of primary and secondary side voltage, current, power, power factor and other electrical parameters for power management and process optimization. 1. CT and VT Type Primary ...

Product Details

Highlight:

EAF Parameter Electrical Measurement Instruments

,

SAF Parameter Electrical Measurement Instruments

,

SAF Electrical Measurement Instruments

Voltage:
0~600V/0~35kV
Current:
0~100,000A
Power:
0~999MW
Power Factor:
0~1
Harmonics:
1~63rd Order
Frequency:
45~65Hz

Product Description

Electrical Parameter Measurement Instruments

SAF and EAF are high-current, low-voltage equipment requiring precise measurement of primary and secondary side voltage, current, power, power factor and other electrical parameters for power management and process optimization.

1. CT and VT

Type Primary Rating Secondary Output Accuracy Class Applications
Current Transformer (CT) 100~100,000A 5A/1A/4~20mA 0.2/0.5/1.0 Primary side high current measurement, secondary current transformation
Voltage Transformer (VT) 6kV/10kV/35kV 100V 0.2/0.5 Primary side high voltage measurement
Rogowski Coil 100~200,000A 0~10V/4~20mA 1.0 High current, non-contact measurement
Hall Effect Current Sensor 0~10,000A 4~20mA/0~10V 0.5/1.0 DC high current measurement

2. Power Quality Analyzer

Parameter Measuring Range Accuracy Features
Voltage 0~600V/0~35kV 0.2% True RMS measurement
Current 0~100,000A 0.5% Input via CT/Rogowski coil
Power 0~999MW 0.5% Active/Reactive/Apparent power
Power Factor 0~1 ±0.02 Per-phase/combined display
Harmonics 1~63rd order Class B THD, individual harmonic content
Frequency 45~65Hz ±0.01Hz Grid frequency monitoring

3. Electrical Parameter Measurement Selection Reference

Measurement Scenario Recommended Instrument Selection Reason
Primary side high current (tens of kA) CT + Power quality analyzer Standard configuration, reliable accuracy
Secondary side high current Rogowski coil / Hall sensor Non-contact, easy installation
Power metering and assessment Power quality analyzer (Class 0.2) High accuracy, meets metering requirements
Harmonic monitoring Power quality analyzer (Class A/B) Meets harmonic mitigation requirements
DC furnace current measurement Hall effect current sensor Specially designed for DC measurement